Bull NovaScale 3005 Series Specifications Page 69

  • Download
  • Add to my manuals
  • Print
  • Page
    / 86
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 68
A-21
Specifications and Features
Power Cables
PDU-2-4-M-32A
AC (32A)
Cable type
Connector type
1 per PDU
3 x AWG10 ( 3 x 6 mm
2
/ #10US)
IEC60309-32A
It is mandatory for power lines and terminal boxes to be located within the immediate vici-
nity of the system and to be easily accessible. Each power line must be connected to a se-
parate, independent electrical panel and bipolar circuit breaker. PDUs require an extra ca-
ble length of 1.5 meters for connection inside the cabinet.
Electrical Specifications
(power supplies are auto-sensing and auto-ranging)
Current draw
Power consumption
Thermal dissipation
11 A max. at 200 VAC input
2400 VA per full CSS module
2400 W / 8190 BTU per full CSS mod-
ule
Europe
Nominal voltage
Voltage range
Frequency
230 VAC (Phase / Neutral)
207 - 244 VAC
50 Hz 1%
United States of America
Nominal voltage
Voltage range
Frequency
208 VAC (Phase / Neutral)
182 - 229 VAC
60 Hz 0.3%
Japan
Nominal voltage
Voltage range
Frequency
200 VAC (Phase / Neutral)
188 - 212 VAC
60 Hz 0.2%
Brazil
Nominal voltage
Voltage range
Frequency
220 VAC (Phase / Neutral)
212 - 231 VAC
60 Hz 2%
Breaker Protection (Mains Power)
PDU-2-4-M-32A
Maximum inrush current
32A Curve C
210A / per quarter period
Table 16. NovaScale 5085 Server specifications