xiv
Site Preparation Guide
Protection against Electrostatic Discharges
CMOS (Complementary Metal Oxide Semiconductor) technology is highly sensitive to
electrostatic discharges. The use of conductive antistatic flooring is strongly recommended.
Maintenance personnel must wear wrist-straps before handling electronic equipment.
A ground socket is provided in each cabinet.
Shocks and Vibrations
The servers comply with standards:
IEC 60068-1
IEC 60068-2-6
IEC 60068-2-27
IEC 60068-2-31
IEC 60068-2-47
IEC 60068-2-64
IEC 60050
ISO 2041
ISO 5348
ISO 5344
ISO 8626
Operating Mode (on levelers)
Sinusoidal vibrations:
- Duration: 1 sweep, 1 octave/mn
- 5 - 16 Hz range: 0.25 mm peak
- 16 -200 Hz range: 0.25 g peak
Random excitation:
- Duration: 15 mn
- Frequency: 5 - 200 Hz
- Spectral density: 1.5x10
-4
g /Hz
- Root mean square acceleration: 0.17g RMS
Non-operating Mode (on castors)
Sweep sine:
- Duration: 1 sweep, 1 octave/mn
- 5 - 16 Hz range: 0.25 mm peak
- 16 - 200 Hz range: 0.25 g peak
Random excitation:
- Duration: 15 mn
- Frequency: 5 - 200 Hz
- Spectral density: 1.5x10
-3
g /Hz
- Root mean square acceleration: 0.54g RMS
Shock Tests:
Duration: 11 ms
Form: 1/2 sinusoidal
Amplitude: 15 g