Bull NovaScale 3005 Series Specifications Page 62

  • Download
  • Add to my manuals
  • Print
  • Page
    / 86
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 61
A-14
Site Preparation Guide
NovaScale 4020 Server CPU Drawer Specifications
Dimensions / Weight
Height 8.77 cm (3.5 in, 2U)
Width 44.9 cm (17.7 in)
Depth 74.7 cm (29.4 in)
Weight 30 kg (65 lb)
Electrical
Power 650 VA
Voltage range (VAC) 200 VAC to 240 VAC nominal,
autoranging +6%, -10%
Frequency 50 to 60 Hz 5%
Current 3 amps
Thermal output (typical) 2300 Btu/hr
Temperature Operating Non-Operating
Dry Bulb Temperature 10 to 35 C -40 to 70 C
(50 to 95 F) (-40 to 158 F)
Gradient Not stated Not stated
Humidity Operating Non-Operating
(non-condensing) Not stated 95% RH, 25 to 30°C
(77 to 86° F)
Gradient Not stated Not stated
Max. Wet Bulb Temperature Not stated Not stated
Moisture Content Not stated Not stated
Noise Emissions (1) System Running System Idle
Sound Power 6.7 BA Not stated
(Dome method)
Sound Pressure 55 dBA N/A
(1) Acoustic tests at room temperature of 28° C (82° F) without failure condition.
Table 12. NovaScale 4020 Server CPU drawer specifications