Page view 55
A-8
Site Preparation Guide
Electrical specifications
(power supplies are auto-sensing and auto-ranging)
Current draw
Power consumption
Thermal dissipation
24 A max. at 240 VAC input per PDU
8800 VA (max. 40U cabinet)
5500 VA (max. 19U cabinet)
5700 VA (max. per PDU)
1500 VA / 5100 BTU (per Novascale 3045 CPU drawer)
Europe
Nominal voltage
Voltage range
Frequency
230 VAC (Phase / Neutral)
207 - 244 VAC
50 Hz ±1%
United States of America
Nominal voltage
Voltage range
Frequency
208 VAC (Phase / Neutral)
182 - 229 VAC
60 Hz ±0.3%
Japan
Nominal voltage
Voltage range
Frequency
200 VAC (Phase / Neutral)
188 - 212 VAC
60 Hz ±0.2%
Brazil
Nominal voltage
Voltage range
Frequency
220 VAC (Phase / Neutral)
212 - 231 VAC
60 Hz ±2%
Breaker Protection
Mains power PDU
Maximum inrush current
20A Curve C
210A/per quarter period
Table 7. NovaScale 3005 Series Server Cabinet Specifications
Page view 55